PF24V Directional Sounder with Voice Messaging
INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL DESCRIPTION
Before installing, please read the Directional Sound Applications Guide, avail-
able through System Sensor. The installation must meet the requirements of
the authority having jurisdiction, CAN/ULC S524 and CSA C22.1. Directional
sounders are used as supplemental signals on a fire alarm system to aid in the
evacuation of building occupants. Although directional sounders may be con-
nected to notification appliance circuits (NAC) for fire alarm service, they are
not a replacement for audible or visible notification appliances as required by
the authority having jurisdiction.
The directional sounder can be installed in systems using 24 Volt DC regulated
power supplies only. It is not approved for use with FWR unregulated power
supplies.
Directional sound is a broadband, multi-frequency sound. The sound source
is easily and quickly located by building occupants, making it ideal for rapid
building evacuation. The sounder incorporates four different speed settings
which consist of broadband noise. The four speed settings can be used to cre-
ate an egress pathway out of a building. The speed setting should be set faster
for units installed at the perimeter exit. In addition to the broadband noise, the
sounder is capable of playing an alert message in the form of a recorded voice
message or other audible signals. These messages will instruct the occupant
of what action to take as they approach the directional sounder. The voice
messages include: exit here, stairs up, stairs down, or area of refuge.
Speed settings are made via DIP switches on the back of the sounder.
POWER SUPPLY CONSIDERATIONS FOR DIRECTIONAL SOUNDERS
Panels typically supply DC filtered voltage or FWR (full-wave rectified) volt-
age. This device is only compatible with DC filtered supplies and must not be
used with panel supplies that are FWR. Be certain the sum of all the device
currents do not exceed the current capability of the panel power supply. Cal-
culations are based on using the device current found in Table 1 and must be
the current specified for the installed settings of the device.
WIRE SIZES
The last device on the circuit must have sufficient voltage to operate the de-
vice within its rated voltage range. When calculating the voltage available to
the last device, it is necessary to consider the voltage drop due to the resis-
tance of the wire. The thicker the wire, the less the voltage drop. Generally,
for purposes of determining the wire size necessary for the system, it is best
to consider all of the devices as “lumped” on the end of the supply circuit
(simulates “worst case”).
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft.
16 AWG solid: Approximately 5 ohms/1,000 ft.
14 AWG solid: Approximately 3 ohms/1,000 ft.
12 AWG solid: Approximately 2 ohms/1,000 ft.
SPECIFICATIONS
Mechanical
Input terminals: 12 – 24 AWG
Sounder size: 4 inches (101mm)
Grille Size: 4
7
/8˝ (127mm)
Electrical
Voltage Input: Regulated 24 Volts DC
Operation Voltage Range: 16 to 33 Volts
Operating Humidity Range: 10% to 93% relative humidity non-condensing
Frequency range: 707 Hz to 11314 Hz
Operating Temperature range: 32° to 120°F (0° to 49°C)
Power: Selectable Low, Med-Low, Medium, Medium-High, High
Listings: UL 464 Directional Sounder, supplemental notification appliance, ULC S524
NOTICE: This manual should be left with the owner/user of the equipment.
Example: Assume you have 10 devices on a zone and each requires 50mA
average and 2000 ft. of 14 AWG wiring (total length = outgoing + return).
The voltage at the end of the loop is 0.050 Amps per device × 10 devices ×
3 ohms/1000 ft. × 2000 ft. = 3 volts drop.
The same number of devices using 12 AWG wire will produce only a 2 volt
drop. The same number of devices using 18 AWG wire will produce an 8 volt
drop. Consult your panel manufacturer’s specifications, as well as the sound-
er’s operating voltage to determine the acceptable voltage drop.
NOTE: If class “A” wiring is installed the wire length may be up to 4 times the
single wire length in this calculation.
TABLE 1. CURRENT DRAW MEASUREMENTS AND SOUND OUTPUT GUIDE:
Speed Selection
Power
Setting
Maximum DC
Operating
Current
(mA RMS)
(16 to 33V)
Audibility
(dBA)
(16 to
33V)
Note 1
Audibility
(dBA)
(16 to
33V)
Note 2Speed
DIP Switch
Selection
FAST (exit) 10 High 185 98 75
FAST (exit) 10 Med-High 131 95 72
FAST (exit) 10 Med 78 92 69
FAST (exit) 10 Med-Low 76 89 66
FAST (exit) 10 Low 64 86 63
MED-FAST 9 High 170 98 74
MED-FAST 9 Med-High 124 95 71
MED-FAST 9 Med 75 93 68
MED-FAST 9 Med-Low 73 90 65
MED-FAST 9 Low 62 87 62
MED-SLOW
8 High 135 97 73
MED-SLOW
8 Med-High 104 95 70
MED-SLOW
8 Med 67 92 67
MED-SLOW
8 Med-Low 65 89 64
MED-SLOW
8 Low 57 87 61
SLOW 7 High 120 98 72
SLOW 7 Med-High 92 95 69
SLOW 7 Med 62 92 66
SLOW 7 Med-Low 61 89 63
SLOW 7 Low 54 86 60
NOTE 1: Sound output data is peak dB measured in ULC anechoic room at 10 feet.
NOTE 2: Sound output measured in a reverberant room at 10 feet.
I56-2961-001R
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
Page view 0
1 2 3 4

Summary of Contents

Page 1 - 8˝ (127mm)

D690-06-00 1 I56-2961-001RPF24V Directional Sounder with Voice MessagingINSTALLATION AND MAINTENANCE INSTRUCTIONSGENERAL DESCRIPTIONBefore installing

Page 2

D690-06-00 2 I56-2961-001RINSTALLATION Consult the ExitPoint Applications Guide (A05-1048-XXX) for information re-garding the appropriate mounting lo

Page 3 - HOUSING. DO NOT LOOP WIRES

D690-06-00 3 I56-2961-001RFIGURE 1.TWO WIRE SYSTEMANY MIX OF MODELSOPTIONAL DISABLE CONTACTNOTE: SWITCH POSITION 4 SETS THIS INPUT TO EITH

Page 4 - ©2013 System Sensor

D690-06-00 4 I56-2961-001R ©2013 System SensorThe directional sounder will not work without power. The directional sounder gets its power from th