D400-55-00 1 I56-691-03
SP100ADA Series Dual-transformer
Speaker/Strobes for Fire Protective
Signaling Systems
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The National Fire Protection Association (NFPA) has pub-
lished standards and recommended practices for the speak-
ers described in this manual. As a result, the installer must
be familiar with these requirements as well as all local
codes and special requirements of the authority having ju-
risdiction.
SP100ADA series speaker/strobes can be operated with dis-
tribution amplifiers having an output voltage of either 25
volts or 70.7 volts.
The speakers operate at any one of six input power levels.
The output sound level is selected at the time of installa-
tion, but can be changed, if necessary.
The speaker is also equipped with a capacitive input to al-
low for DC supervision.
The SP100ADA Series Speaker/Strobe is equipped with an
attached 15, 15/75, 75, or 110 candela (cd), UL 1971 listed
strobe. Although they are shipped as a unit, the strobe and
speaker are electrically independent and require separate
power sources. Strobes can be powered by means of a 24V
regulated or full-wave rectified unfiltered supply.
Installation - For Strobe Replacement See NFPA 72,
Chapter 6
All wiring must be installed in compliance with the Na-
tional Electrical Code and all applicable local codes as well
as any special requirements of the authority having juris-
diction, using the proper wire size. This also includes all
applicable NFPA Standards, ANSI/UL 1480, and NEC 760.
Figure 1. Electrical connections:
Specifications
Mechanical
Input Terminals: 12 to 18 AWG (3.31 to 0.82 mm
2
)
Speaker Size: 4 inches (101 mm)
Grille Size: 5" (127 mm) square
Electrical (Speaker)
Voltage Input: 25 volts or 70.7 volts (nominal)
Frequency Range: 400 - 4000 Hz
Operating Temperature Range: 32° to 120°F (0° to 49°C)
Electrical
1. Connect the speaker/strobe as shown in Figure 1. Keep
in mind that even though the speaker and strobe are a
single mechanical unit, they are electrically independent
and require separate power sources.
NOTE: Do NOT loop electrical wiring under terminal
screws. Wires connecting the device to the control
panel must be broken at the device terminal con-
nection in order to maintain electrical supervision.
2. Notice that the speaker circuit board is equipped with
two sets of posts and associated electrical jumper wires.
One set of posts is numbered 1 through 6 while the other
is labeled A and B. Both electrical leads are fitted with a
barrel connector. These two sets of posts and leads en-
able the installer to select any one of six sound pressure
levels with either a 25 volt or 70.7 volt amplifier.
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Signaling Systems

D400-55-00 1 I56-691-03SP100ADA Series Dual-transformerSpeaker/Strobes for Fire ProtectiveSignaling SystemsINSTALLATION AND MAINTENANCE INSTRUCTIONSA

Page 2 - D400-55-00 2 I56-691-03

D400-55-00 2 I56-691-03 For example, Table 1 shows that to select a 1/4 Watt in-put when a 25 volt amplifier is being used, slide the bluelead on

Page 3 - D400-55-00 3 I56-691-03

D400-55-00 3 I56-691-03LIGHT0˚–45˚45˚90˚ –90˚Figure 3:Degrees % of Rating01005 - 25 9030 - 45 7550 5555 4560 4065 3570 3575 3080 3085 2590 25Table 2.

Page 4

D400-55-00 4 I56-691-03 © System Sensor 1996If either of the power option jumper wires is not plugged into one of theappropriate option positions, th