Magnetic Testing
To attach the magnet to the pole:
1. Pull the connecting pin and remove the Installation/
Removal head from the pole assembly.
2. Push and hold the lock button, and remove the con-
necting tube from the pole.
3. Remount the other end of the connecting tube to the
pole, making sure that the lock button snaps into place.
4. Slide the magnet into the slots and cover with the plastic
cap.
To Test The Detector:
1. Hold the test magnet near the raised mark on the smoke
detector in one of the test areas shown in Figure 3.
NOTE: If the smoke detector does not alarm after 20 sec-
onds, move the magnet to the other test area and
repeat.
2. Smoke detector LEDs should light and panel should in-
dicate alarm.
3. Push the reset button on the panel to reset the smoke
detector.
4. See the smoke detector manual for additonal infor-
mation.
WARNING
When using the XR2B removal tool with the XP-4 extension
poles, avoid any contact with overhead wiring. The wood
insulators in the extension poles are not effective in all
shock hazard situations.
Figure 2. Insertion of detector head
into cup of XR2B:
LED Status
Indicators
Magnet Test
Marker
Te
st Magnet
Position
Te
st Magnet
Position
Magnet Test
Marker
Figure 3. Test Magnet Position:
C0145-00
C0184-00
2 I56-2248-00