SS-450-006 1 I56-3741-001R
EBR Plug-in
Relay Detector Base
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEFORE INSTALLING
Please read the System Smoke Detector Applications Guide, which provides
detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications. Copies of this application guide are available from System
Sensor. NFPA 72 guidelines should be observed.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The relay base is intended for use with intelligent systems. Refer to the panel
manual for maximum allowable number of units per loop.
Form C latching relay contacts are included for the control of an auxiliary
function.
SPECIFICATIONS
Base Diameter: 6.85 in (17.4 cm)
Base Height (less sensor): 1.61 in (4.1 cm)
Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 10% to 93% Relative Humidity (Non-condensing)
Electrical Ratings
Operating Voltage: 15 to 32 VDC
Standby Current: 170 µA
Relay Characteristics
Coil: 2 coil latching
Contact Type: Form C
Contact Relay Ratings
Set Time: 20 msec
Reset Time: 250 msec
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC Resistive Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
I56-3741-001R
1
2
3
4
5
6
FIGURE 1. TERMINAL LAYOUT:
CO471-04
BASE TERMINALS
NO. FUNCTION
1. Normal Close
2. Common
3. Normal Open
4. Comm. (–)
5. Comm. (+) In/Out
6. Comm. (+) Out/In
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Relay Detector Base

SS-450-006 1 I56-3741-001REBR Plug-in Relay Detector BaseINSTALLATION AND MAINTENANCE INSTRUCTIONS3825 Ohio Avenue, St. Charles, Illinois 601741-800-

Page 2 - MOUNTING

SS-450-006 2 I56-3741-001RMOUNTINGMount the mounting plate directly to an electrical box. The plate will mount directly to 4-inch square, 4-inch octa

Page 3 - Comm.(–)

SS-450-006 3 I56-3741-001RC0890-03LISTED COMPATIBLE CONTROL PANELCLASS A OPTIONAL WIRING2 RELAY COMMON1 NORMALLY CLOSED3 NORMALLY OPENSLC (+)SLC (–)

Page 4 - ©2011 System Sensor

SS-450-006 4 I56-3741-001R ©2011 System SensorTHREE-YEAR LIMITED WARRANTYSystem Sensor warrants its enclosed smoke detector base to be free from

Comments to this Manuals

No comments