System-sensor DH100LP User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Wiring Instructions
The DH100LP detectors are designed for easy wiring. The
housing provides a terminal strip with clamping plates.
Wiring connections are made by stripping about
3
/8˝ of in-
sulation from the end of the wire, sliding the bare end un-
der the plate, and tightening the clamping plate screw.
The DH100LP duct smoke detector is designed to operate
with 12 or 24 VDC UL listed 2-wire compatible control pan-
els. Alarm current must be limited by the control panel to
100mA or less. An example of a UL listed compatible con-
trol panel is the Fire-Lite model Sensiscan 1000 using zone
card ANC-2 and compatibility identification A. Install per
installation instruction S1000/801. A maximum of 20 detec-
tors may be installed per zone.
[5.7] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section [6.2.1].
2. Perform MAGNET TEST per Section [6.2.2.1]. The
RTS451 test of Section [6.2.2.2] may substitute for
this requirement.
3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].
[5.8] Install The Cover
Install the cover using the six screws that are captured in
the housing cover. Be certain filters are installed as speci-
fied in Section [5.5]. Make sure that the cover fits into the
base groove and that all gaskets are in their proper posi-
tions. Tighten the six screws.
[6] Duct Smoke Detector Maintenance And
Test Procedures
Test and maintain duct smoke detectors as recommended in
NFPA 72. The tests contained in this manual were devised
to assist maintenance personnel in verification of proper
detector operation.
Before conducting these tests, notify the proper authorities
that the smoke detection system will be temporarily out of
service. Disable the zone or system under test to prevent
unwanted alarms.
[6.1] Smoke Entry Tests
[6.1.1] Air Flow
The DH100LP is designed to operate over an extended air
speed range of 100 to 4000 FPM. To verify sufficient sam-
pling of ducted air, turn the air handler on and use a manom-
eter to measure the differential pressure between the two
sampling tubes. The differential pressure should measure at
least 0.0015 inches of water and no more than 1.2 inches
of water. Because most commercially available manometers
cannot accurately measure very low pressure differentials,
applications with less than 500 FPM of duct air speed may
require one of the following: 1) the use of a current-sourcing
pressure transmitter (Dwyer Series 607) per Section 6.1.4 or;
2) the use of aerosol smoke per section 6.1.2.
[6.1.2] Air Flow Test using Aerosol Smoke
This test is intended for low-flow systems (100-500FPM).
If the air speed is greater than 500FPM, use a conventional
manometer to measure differential pressure between the
sampling tubes as described in 6.1.1. Drill a
1
4˝ hole 3 feet
upstream from the duct smoke detector. With the air han-
dler on, measure the air velocity with an anemometer. Air
speed must be at least 100 FPM. Spray aerosol smoke* into
the duct through the
1
4˝ hole for five seconds. Wait two
minutes for the duct smoke detector to alarm. If the duct
smoke detector alarms, air is flowing through the detector.
Remove the duct smoke detector cover and blow out the re-
sidual aerosol smoke from the chamber and reset the duct
smoke detector. Use duct tape to seal the aerosol smoke
entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries,
Malibu, CA. Phone: 310/457-5813.
[6.1.3] Smoke Entry Test
To determine if smoke is capable of entering the sensing
chamber, visually identify any obstructions. Plug the ex-
haust and inlet tube holes to prevent ducted air from carry-
ing smoke away from the detector head, then blow smoke
such as cigarette, cotton wick, or punk directly at the head
to cause an alarm. REMEMBER TO REMOVE THE PLUGS
AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNC-
TION PROPERLY.
[6.1.4] Air Flow Test using Dwyer Series 607 Differ-
ential Pressure Transmitter
Verify the air speed of the duct using an anemometer. Air
speed must be at least 100 FPM. Wire the Dwyer transmit-
ter as shown in Figure 7. Connect the leads of the meter
to either side of the 1000Ω resistor. Allow unit to warm up
for 15 seconds. With both HIGH and LOW pressure ports
open to ambient air, measure and record the voltage drop
across the 1000Ω resistor (measurement 1), 4.00 volts is
typical. Using flexible tubing and rubber stoppers, connect
the HIGH side of the transmitter to the sampling tube of
the duct smoke detector housing, and the LOW side of the
transmitter to the exhaust tube of the duct smoke detec-
tor housing. Measure and record the voltage drop across
the 1000Ω resistor (measurement 2). Subtract the voltage
recorded in measurement 1 from the voltage recorded in
measurement 2. If the difference is greater than 0.15 volts,
there is enough air flow through the duct smoke detector
for proper operation.
D200-15-00 5 I56-0083-009R
Page view 4
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments