SS-300-022 1 I56-3936-003R
D4240 Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
TABLE OF CONTENTS PAGE
[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2]
Exploded View of Duct Smoke Detector Components
.............2
[3] General Description ......................................2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation .................................3
[7] Measurement Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Unit Configuration .......................................5
[10] Detector Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[11] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 6
[12] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Detector Cleaning Procedures ..............................7
[14] Sensor replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[15] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
BEFORE INSTALLING
Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct
Applications (A05-1004), which provides information on detector spacing,
placement, zoning, wiring, and special applications. This manual is available
online at www.systemsensor.com. NFPA Standards 72 and 90A should also be
referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
I56-3936-003R
SPECIFICATIONS
Operating Temperature: D4240: –4° to 158° F (–20° to 70° C)
Storage Temperature: D4240: –22° to 158° F (–30° to 70° C)
Humidity: 0% to 95% Relative Humidity Non-condensing
Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
D4240 Footprint Dimensions: Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)
Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)
D4240 Weight: 2.5 pounds; 1.14 kg
Electrical
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 240 VAC 50-60 Hz
Input capacitance: 270 µF max. 270 µF max. N/A
Reset Voltage: 3.0 VDC min. 2.0 VAC min. 20 VAC min.
Reset Time (with RTS451/RTS151): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec.
Reset Time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power Up Time: 35 sec. max. 35 sec. max. 35 sec. max.
Alarm response time: 15 sec. 15 sec. 15 sec.
Sensitivity Test: See detector label See detector label See detector label
Current Requirements (Using No Accessories)
Max. standby current 21 mA @ 24 VDC 65 mA RMS @ 24VAC 60Hz 10 mA RMS @ 240 VAC 60 Hz
Max. alarm current 65 mA @ 24 VDC 135 mA RMS @ 24 VAC 60 Hz 18 mA RMS @ 240 VAC 60 Hz
CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VDC (resistive)
Alarm auxiliary contatcs (DPDT) 10A @30 VDC (resistive)
10A @250 VAC (resistive)
1
/2 HP @240 VAC
1
/4 HP @120 VAC
NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of
control panels. Use the alarm initiation contact for this purpose.
Supervisory Contacts (SPDT) 2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY TROUBLE ALARM
APA151/APA451 12.5mA n/a 30mA Max.
MHR/MHW 0mA n/a 29mA Max.
RA400Z/RA100Z 0mA n/a 12mA Max.
RTS451/RTS151 0mA n/a 12mA Max.
RTS451KEY/RTS151KEY 12mA n/a 12mA Max.
SSK451/RTS2-AOS 8mA Max. 16mA Max. 40mA Max.
NOTE: Any combination of accessories may be used such that the given
accessory loads are: 110mA or less at the Aux output, and 50mA or less
at the Alarm output.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
[1] LIMITATIONS OF DUCT SMOKE DETECTORS
WARNING
The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The D4240 Air Duct Smoke Detectors
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual. Failure
to comply with these requirements may prevent the detector from activating
when smoke is present in the air duct.
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - D4240 Duct Smoke Detector

SS-300-022 1 I56-3936-003RD4240 Duct Smoke DetectorINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSO

Page 2 - H0549-11

SENSOR MODULE COVERPOWER BOARDMODULE COVERSENSOR HEADMETAL SAMPLING TUBEPOWER BOARDEXHAUST TUBEVARISTOR4-WIREMAGNET TEST LOCATION(sold seperately)[3]

Page 3 - H0215-00

[6] SAMPLING TUBE INSTALLATION [6.1] SAMPLING TUBE SELECTIONThe sampling tube must be purchased separately. Order the correct length, as specified in

Page 4 - SENSOR 2

[8] FIELD WIRING INSTALLATION GUIDELINESAll wiring must be installed in compliance with the National Electrical Code and the local codes having jurisd

Page 5 - H0558-10

SS-300-022 5 I56-3936-003RFIGURE 7. SYSTEM WIRING DIAGRAM FOR 4-WIRE DUCT SMOKE DETECTORS:CAUTIONDo not loop wire under terminals when wiring detecto

Page 6 - 4 inch hole

SS-300-022 6 I56-3936-003RFIGURE 8. MULTIPLE FAN SHUTDOWN (INTERCONNECTION OF D4240’S):DETECTOR 1240 VACD4240C, AUX ANC, AUX A50DET. MAX.INT/AUX–IN

Page 7 - (RED LED) ALARM

109192011215321D4240APA151/451(GREEN LED) POWERFIELD INSTALLED JUMPER112+–AUX OUT +AUX OUT –ALARMR TESTACC +ACC –R RESET7188176161431354SUP, NOSUP, CN

Page 8 - ©2012 System Sensor

THREE-YEAR LIMITED WARRANTYSystem Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and servi